GMV5 Heat Recovery- Technical Specifications

Print Friendly, PDF & Email
Model GMV-Q224WM/B-X GMV-Q280WM/B-X GMV-Q335WM/B-X GMV-Q400WM/B-X GMV-Q450WM/B-X
Capacity Range 8 HP 10 HP 12 HP 14 HP 16 HP
Capacity kW 22,40 25,00 28,00 31,50 33,50 37,50 40,00 45,00 45,00 50,00
Capacity Btu/h 76.429 85.300 95.536 107.478 114.302 127.950 136.480 153.540 153.540 170.600
Consumption W 5,20 5,30 6,90 7,30 8,20 8,70 10,60 10,80 12,10 12,50
Current Input (Nom) A 9,30 9,50 12,30 13,00 14,70 15,60 18,90 19,30 21,60 22,30
EER - COP - Class W/W 4,07 4,17 3,73 3,89 3,76 3,68 3,54 3,85 3,33 3,62
Ambient Temperature Range oC -5~52 -20~24 -5~52 -20~24 -5~52 -20~24 -5~52 -20~24 -5~52 -20~24
Heat Recovery Mode -10~20 -10~20 -10~20 -10~20 -10~20
Power Supply V-Ph-Hz 380-415V ~ 3N - 50 Hz 380-415V ~ 3N - 50 Hz 380-415V ~ 3N - 50 Hz 380-415V ~ 3N - 50 Hz 380-415V ~ 3N - 50 Hz
Power Connection Cable ODU-IDU/ Com. mm2 5×2,5 5×2,5 5×4,0 5×6,0 5×6,0
Sound Pressure Level dB(A) 60 61 63 63 63
Air Flow Volume m3/h 11.400 / 1 11.400 / 1 14.000 / 2 14.000 / 2 14.000 / 2
Compressor Type/ Number HITACHI Scroll Inverter / 1 HITACHI Scroll Inverter / 1 HITACHI Scroll Inverter / 1 HITACHI Scroll Inverter / 2 HITACHI Scroll Inverter / 2
Refrigerant Charge R410 - 6,20kg R410 - 7,10kg R410 - 9,60kg R410 - 11,10kg R410 - 11,60kg
Diameter Liquid-Gas Connection Pipe inch 3/8″ - 5/8” - 3/4″ 3/8″ - 3/4” - 7/8″ 1/2″ - 3/4” - 1″ 1/2″ - 7/8” - 1″ 1/2″ - 7/8” - 1 1/8″
Max IDU’s Units 13 16 19 23 26
Unit Dimension LxHxD/ Weight mm/kg 930x1605x765 / 233 930x1605x765 / 233 1340x1605x765 / 303 1340x1605x765 / 360 1340x1605x765 / 360